Corrosion Inhibitor Multifunctional Closed Chilled Systems

Home / Products / Cooling Water Chemical / Corrosion Inhibitor Multifunctional Closed Chilled Systems
IMPA / ISSA CERTIFIED CHEMICAL FORMULATION

Corrosion Inhibitor Multifunctional Closed Chilled Systems

Cooling Water Chemical Corrosion Inhibitor Multifunctional Closed Chilled Systems
Express Kolkata & Haldia Port 2-4 Hr Berth Delivery
Cooling Water Chemical
Part No. / SKU: RXSOL-40-4011-025

Premium Quality Alkaline Corrosion Inhibitor blend for Metal protection inside the CLOSED circulating system

Available Packaging:
Ready stock available in 5 Litre, 20L, 25L, 210 Litre HDPE drums and 1000L IBC Totes.
Ready Port Stock 25L, 210L Drums & 1000L IBC
IMPA / ISSA Standard MARPOL Compliant Formulations
ISO 9001:2015 QA TDS, MSDS & COA Available

Application & Uses

Application-DG Sets:-Internal combustion engines closed circuit cooling system compressor cooling system.RXSOL-40-4011-256 incorporates superior corrosion inhibitors to prevent corrosion works by free of scale deposits.

Corrosion Inhibition for mixed-metallurgy closed cooling systems, including:

 

  • HVAC chilled and hot water systems
  • Industrial closed cooling loops
  • Engine jacket water systems
  • Heat exchangers and cooling circuits
  • Power plant auxiliary cooling systems

Dosage & Directions for Use

Method Of Use:-1. Properly clean the system with water and alkaline liquid , if necessary.
2. Add 0 .05-0.2 % of RXSOL-40-4011-256 in system or recommended Nitrite level 1400 – 2500 ppm can be measured and controlled by any standard RXSOL test kit for Nitrite, Chloride test also helps to detect excess contamination to maintain accepted levels . when the product is dosed as recommended limit By buffering action of RXSOL-40-4011-256, pH should be maintained between 8.3 and 10 by the treatment.

Note:- Initial dosage for an untreated system is 7 Kg of RXSOL-40-4011-256/ 1000 litres of untreated distilled water. This will bring the treatment up to the minimum level of 1000 ppm nitrite. For best result and prolonged engine life add RXSOL-40-4011-256 every 500 -6500 km. or 250 to 300 hours of running time or every 2 month interval .

These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship. • Department issuing data specification sheet Environment protection department.

Product Description & Chemical Profile

RXSOL-40-4011-025 is a liquid, Nitrite/Borate based compound with unique formulation with organic Corrosion Inhibitors, Anti-Scalant for use in closed cooling water systems, for preventing corrosion and scale Formation in Internal combustion engines, compressor cooling system, DG -set at high or low temperature. It is also acts as a corrosion inhibitor Protects all the metals including cast iron, mild steel, copper etc.

RXSOL Corrosion Inhibitor Multi Metal is a high-performance, molybdate-based multi-metal corrosion inhibitor formulated specifically for closed cooling water systems operating under high temperature and high heat flux conditions. The product is a synergistic blend of molybdate, nitrite, azole, scale inhibitors, and dispersants, designed to provide rapid passivation and long-term corrosion protection for mild steel, copper, and copper alloy metallurgies commonly found in closed-loop systems. It also controls scale formation and particulate fouling, ensuring clean heat transfer surfaces and improved system efficiency.

Kolkata & Haldia Port Logistics Desk

Need pricing, bulk volume, or vessel delivery today?

Send us your required quantity, chemical grade, delivery location, or vessel IMO number. Our technical chemical supply team replies within 1 hour.

Need a quote for this product?

Tell us the grade, packing and quantity you need — we ship across India and to major ports.

Request a quote chemicalkolkata @ gmail.com